DS-N M/W
|
Technical data
Maximum continuous voltage AC (V) | 130 |
Protection rating | IP40 |
Maximum continuous voltage DC (V) | 185 |
Category | Type 1+2 / D1+C2 |
Lightning protection zone LPZ | 0→2 |
Number of poles | 1 |
Rated current (A) | 10 |
Wave resistance (Ω) | 50 |
Capacity (wire-wire) | <10 pF |
Capacity (wire-earth) | <20 pF |
Impulse durability wire-wire | C2: 10 kV / 5 kA (8/20µs) |
Impulse durability wire-earth | C2: 10 kV / 5 kA (8/20µs) |
Total discharge current (8/20) (kA) | 10 |
Total discharge current (10/350) (kA) | 5 |
Protection level wire-wire (V) | <800 |
Protection level wire-earth (V) | <800 |
Impulse discharge current (10/350) (kA) | 2.5 |
Protection level (V) | <800 |
Frequency range | 0 - 3 GHz |
Insertion loss (dB) | ≤0,62 |
Return loss (dB) | ≥14 |
Temperature range (°C) | -40 - +80 |
Installation type | Connector/cable adapter |
Connection system | N |
Shielding connection available | Yes |
Shield connection | Direct |
Testing standard | IEC 61643-21 |
Tender text
Protection deviceCoaxial data cable protection devices
• High pulsed current carrying capacity 2 x 2.5 kA (10/350)
• Simple mounting (adapter plug), m = plug/f = female connector
• Optimised transmission behaviour
• 5-year guarantee
• With N connector
• Including OBO M25 Quick clip for simple installation
Fabrikat: OBO BETTERMANN
Type: DS-N M/W
Item No.: 5093996
Einheit: