Surge protection

FRD 24 HF

Type Weight
kg/100 pcs.
Art. no.
FRD 24 HF 4.4 5098575
Lightning barrier with HF applications

Technical data

Maximum continuous voltage AC (V) 19
Protection rating IP20
Maximum continuous voltage DC (V) 28
Category Type 1+2+3 / D1+C2+C1
Lightning protection zone LPZ 0→3
Number of poles 2
Rated current (A) 0.45
Series resistance per wire 2,2 Ω ± 10 %
Capacity (wire-wire) <40 pF
Capacity (wire-earth) <40 pF
Impulse durability wire-wire C2: 18 kV / 9 kA (8/20µs)
Impulse durability wire-earth C2: 18 kV / 9 kA (8/20µs)
Total discharge current (8/20) (kA) 18
Total discharge current (10/350) (kA) D1: 6
Protection level wire-wire (V) <120
Protection level wire-earth (V) <650
Frequency range 0 - 100 MHz
Insertion loss (dB) ≤3
Temperature range (°C) -40 - +80
Installation type Hat rail 35 mm
Connection system Terminal
Division unit TE (17.5 mm) 1
Earthing via: Terminal
Shielding connection available No
Testing standard IEC 61643-21
Connection cross-section, flexible (mm²) 0.14 - 2.5
Connection cross-section, multi-wire (mm²) 0.14 - 2.5
Connection cross-section rigid (mm²) 0.14 - 2.5

Tender text

Lightning barrier

Surge protection for use in measuring, control and regulation systems.

• Basic, medium and fine protection
• Two-stage protection circuit with high lightning current carrying capacity
• High transmission frequency up to 100 MHz
• Suitable for all bus systems (e.g. Profibus)
• With installation-friendly, screwless connection terminals
• In space-saving 17.5 mm grid

Application: Multipurpose use on any 35 mm DIN profile rail in every commercially available distribution housing.

Fabrikat: OBO BETTERMANN
Type: FRD 24 HF
Item No.: 5098575

Einheit:
1.1.2