TKS-B
|
Technical data
Maximum continuous voltage AC (V) | 120 |
Protection rating | IP20 |
Maximum continuous voltage DC (V) | 170 |
Category | Type 1+2 / D1+C2 |
Lightning protection zone LPZ | 0→2 |
Number of poles | 2 |
Rated current (A) | 20 |
Capacity (wire-wire) | <10 pF |
Capacity (wire-earth) | <10 pF |
Impulse durability wire-wire | C2: 18 kV / 9 kA |
Impulse durability wire-earth | C2: 18 kV / 9 kA |
Total discharge current (8/20) (kA) | 18 |
Total discharge current (10/350) (kA) | D1: 6 |
Protection level wire-wire (V) | <950 |
Protection level wire-earth (V) | <600 |
Frequency range | 0 - 250 MHz |
Insertion loss (dB) | 3 dB @ 250 MHz |
Temperature range (°C) | -40 - +80 |
Installation type | DIN rail |
Connection system | Terminal |
Division unit TE (17.5 mm) | 1 |
Earthing via: | Connection cable |
Shielding connection available | No |
Testing standard | IEC 61643-21 |
Connection cross-section, flexible (mm²) | 0.14 - 2.5 |
Connection cross-section, multi-wire (mm²) | 0.14 - 2.5 |
Connection cross-section rigid (mm²) | 0.14 - 2.5 |
Tender text
Lightning barrierTKS-B: Surge protection for use in measuring, control and regulation systems, as well as telecommunication systems
• Basic protection for lightning protection equipotential bonding
• High impulse arresting capacity 6 kA (10/350)
• With installation-friendly, screwless connection terminals
• In space-saving 17.5 mm grid
Application: Universal use on 35 mm hat profile rail in any standard distributor housing.
Fabrikat: OBO BETTERMANN
Type: TKS-B
Item No.: 5097976
Einheit: